had small layer of oil building on surface of seperator chamber, less than 1/2", not enough to skim. no floating solids. no discharge into ditch. ditch dry, good vegatative growth. no standing water, no visual signs of oily residue. soil light brown in color.
Condition or appearance
had small layer of oil building on surface of seperator chamber, less than 1/2", not enough to skim. no floating solids. no discharge into ditch. ditch dry, good vegatative growth. no standing water, no visual signs of oily residue. soil light brown in color.
Other observations
Additional maintenance needed
Additional information
lift station approx 3/4 full, high float alarm passed visual and audio test. tested operation of both pumps in lift station. Pump #1, circuit energized, pump didn't operate. Tested pump #2, passed, good pumping flow rate into seperator chamber. Re-test pump #1, circuit energized, pump doesn't operate. tested pump #2 again, pumped out lift station to approx 1/4 full. re-test 3rd time pump#1, failed, pump needs repaired or replaced. Advised Store FM, Sam Tahour.